Model # 6207-30-00

Internet #202262419

Store SKU #296046

AFC Cable Systems 2 in. x 100 ft. Liquidtight Flexible Steel Conduit
0077680148087

AFC Cable Systems

2 in. x 100 ft. Liquidtight Flexible Steel Conduit

  • Made with sunlight resistant materials
  • The PVC jacket is flame retardant
  • Versatility to be used in many conditions
$354.00 /each

Frequently Bought Together

Product Overview

The PVC-encased AFC Cable Systems Liquidtite 2 in. x 100 ft. Flexible Steel Conduit is designed to hold power, control and communications cables in dry, wet or oily locations.

  • Helps shield power, control and communications cables from heat, moisture, oil and sunlight
  • Rugged PVC jacket allows for burial in earth or for concrete encasement
  • Hot-dipped zinc, galvanized low-carbon steel core
  • Permanent circuit ground protection provided through a continuous copper bonding strip
  • Separate grounding conductor required (sold separately)
  • UL- and CSA listed
  • Made in USA

Specifications

Dimensions

Details

Warranty / Certifications

More Products With These Features

Search

Customer Questions & Answers

would this coduit have the capacity of 440 volts

Asked by: Jay
AFC Cable Systems UL listed Liquid-Tight Flexible Metal Conduit products are manufactured in accordance with the UL Standard for Liquid-Tight Flexible Metal Conduit UL 360 under File number E26540 for use in accordance with the National Electrical Code. There is no voltage rating attributed to LFMC. Any voltage restriction would be dependent upon the specific application of the Liquidtight Flexible Metal Conduit as permitted by the National Electrical Code. Section 300.2 of the NEC covers Voltage limitations and reads as follows. 300.2 Limitations. (A) Voltage. Wiring methods specified in Chapter 3 shall be used for 1000 volts, nominal, or less where not specifically limited in some section of Chapter 3. They shall be permitted for over 1000 volts, nominal, where specifically permitted elsewhere in this Code. Liquid-Tight Flexible Metal Conduit (LFMC) is covered by Article 350 of the NEC and is a Chapter 3 wiring method. The voltage limitations of NEC Section 300.2 applies to UL Listed Liquid-Tight Flexible Metal Conduit (LFMC).
Answered by: AFCSupport
Date published: 2015-09-30
  • y_2017, m_3, d_26, h_14CST
  • bvseo_bulk, prod_bvqa, vn_bulk_1.0.0
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_1
  • loc_, sid_202262419, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING), SortEntry(order=LAST_APPROVED_ANSWER_SUBMISSION_TIME, direction=DESCENDING), SortEntry(order=LAST_APPROVED_ANSWER_SUBMISSION_TIME, direction=DESCENDING), SortEntry(order=BEST_ANSWER_FEEDBACK_COUNT, direction=DESCENDING), SortEntry(order=POSITIVE_ANSWER_FEEDBACK_COUNT, direction=DESCENDING), SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_homedepot
  • bvseo_sdk, java_sdk, bvseo-3.1.1
  • CLOUD, getContent, 23ms
  • QUESTIONS, PRODUCT

Customer Reviews

  • bvseo_sdk, java_sdk, bvseo-3.1.1
  • CLOUD, getContent, 46ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;