The Reliance Controls Transfer Switch Kit offers a quick, safe, and straightforward way to connect emergency power to homes, offices, stores, or farms. Designed for professional electricians, the kit includes a Pro Tran 2 manual transfer switch (six or ten circuits), a 30A power inlet box, a 10' outdoor-rated generator power cord, and wire connectors, compatible with portable generators with 125/250VAC 20A or 30A locking outlets. Ideal for coastal areas with its non-metallic power inlet box, these transfer switches are cUL 1008 listed and assembled in the USA.
Product Depth (in.) | 4.5 in |
|---|---|
Product Width (in.) | 11.75 in |
Automatic/Manual | Manual |
|---|---|
Fused | Fused |
Included | Cover, Inlet Box, Power Cord |
Maximum Amperage (A) | 30 |
NEMA Configuration | NEMA 1 |
Number of Circuits | 10 |
Phase Type | 1 Phase |
Product Weight (lb.) | 19 lb |
Returnable | 90-Day |
Voltage (V) | 125/250 |
Certifications and Listings | UL Listed |
|---|---|
Manufacturer Warranty | 5 year limited warranty |
Hello Dave, No, the Power Boost in the Ford is a bonded neutral and will trip the GFCI on the F150; We recommend the X -SERIES of Transfer Panels. https://reliancecontrols.com/search-result/xrk
Hello Tim The Transfer Switch that is sold by Home Depot is either the 3006HDK or 310CRK (kits) and have a double pole 20A breaker installed in position A&B. That 20A Breaker can be swapped for a 30A in Postion A&B only - Note all other breaker positions in both Transfer Switch Kits are rated for 20A each.
Depends on if the circuit is ran in 14-2 or 12-2 wire. You shouldn’t use a 20A breaker if the circuit is ran in 14-2. You could buy a 15A breaker to put into the transfer switch.
HELLO. Yes with the understanding that if you are experiencing nuisance breaker trips with the 15A, you would need to replace the 15A breaker with a 20A breaker
Hello Bob, Yes provided you are using only the 30A-240V outlet
Hello, Yes, You would need to verify the out Configuration of the EcoFlow is a L14-30 If not an Adapter Cord will make the connection.
Yes if your generator has 240v output- 6 circuit transfer switch has a 30a 240v breaker. This would be why most people buy it.
Hello Sam, Yes, The wiring from the Transfer Switch to the Main Breaker Panel, You will also need to wire in the inlet box that would be mounted outside, That wire is not included in the Kit,