Brand | Eaton | Square D | Square D | Square D |
Name | CSR 200 Amp 2-Pole 25 kAIC Main Circuit Breaker | QO 200 Amp 10kA 2-Pole Bolt-On QOM2 Frame Size Main Circuit Breaker | PowerPact 200 Amp 10kA 2-Pole Q-Frame Molded Case Circuit Breaker | PowerPact 200 Amp Q-Frame Molded Case 2-Pole Circuit Breaker |
Price | ||||
Ratings | (16) | (6) | (12) | (7) |
Interruption Type | Standard Trip | Standard Trip | Standard Trip | Standard Trip |
Breaker Type | Double Pole | Double Pole | Double Pole | Double Pole |
Pack Size | 1 | 1 | 1 | 1 |
Maximum Amperage (amps) | 200 | 200 | 200 | 200 |
Power Distribution Features | No Additional Features | Trip Indicator | No Additional Features | No Additional Features |
Voltage (volts) | 120/240 | 120/240 | 120/240 | 120/240 |
Mounting Type | Bolt On | Bolt On | Bolt On | Bolt On |
Product Weight (lb.) | 2.55 | 2.59 | 3.24 | 3.53 |
Electrical Product Type | Breaker | Breaker | Breaker | Breaker |
View Product | View Product | View Product | View Product |
![]() | ![]() | ![]() | ![]() | |
Brand | Eaton | Square D | Square D | Square D |
Name | CSR 200 Amp 2-Pole 25 kAIC Main Circuit Breaker | QO 200 Amp 10kA 2-Pole Bolt-On QOM2 Frame Size Main Circuit Breaker | PowerPact 200 Amp 10kA 2-Pole Q-Frame Molded Case Circuit Breaker | PowerPact 200 Amp Q-Frame Molded Case 2-Pole Circuit Breaker |
Price | ||||
Ratings | (16) | (6) | (12) | (7) |
Interruption Type | ||||
Breaker Type | ||||
Pack Size | ||||
Maximum Amperage (amps) | ||||
Power Distribution Features | ||||
Voltage (volts) | ||||
Mounting Type | ||||
Product Weight (lb.) | ||||
Electrical Product Type | ||||
View Product | View Product | View Product | View Product |
Hello, yes this breaker can replace a BW2200, as they have the same frame. Regards, Eaton
Hello Mike, the CSR cannot be installed in a main lug loadcenter. We recommend contacting our technical support team if you have any further questions, 877-386-2273, Opt 2, Opt 3, Opt 1.Regards, Eaton
Hello Marty, we do not have a dual lug kit. The lug capacity on the CSR2200 is (1) #2-300 kcmil. Regards, Eaton
Hey Tony, the main breaker in your house panel should use a CSR2200, and the secondary main breaker would use a CSR2200 as well. Regards, Eaton
Hello Rick, CSR2200N will replace type CSR 200A main breakers. Regards, Eaton.
Hello Bill, CSR2200N can be used as the main for panel BR4080NLQN200G. Regards, Eaton.
Hello Bill. The CSR main breaker will not fit in this panel. You can back feed a CH breaker to act as the main. You will need a hold down kit as well. Regards, Eaton.
Hello Del. The lugs for CSR2200 are rated for #1-300 wire size, so 2/0 would be compatible. Regards, Eaton.
Hello Tom, CSR2200N is the catalog number you can order. The "N" indicates that this is main breaker. Regards, Eaton
3BR4242L225 is a main lug loadcenter, so it does not have a provision for a main breaker to be installed. This panel will not take CSR2200N. For an equivalent main breaker loadcenter, use 3BR4242B225. This loadcenter comes with a CC3225 main circuit breaker installed. Regards, Eaton